Buy AM4-A3A3A3A2-30-30-20-6-3 Part of Eaton Corp with NSN 5925-01-170-1532
MPN: AM4-A3A3A3A2-30-30-20-6-3
Alternate P/N: AM4A3A3A3A230302063
Manufacturer: Eaton Corp
NSN: 5925-01-170-1532
Item Name: Circuit Breaker
CAGE Code: 74193
Part number AM4-A3A3A3A2-30-30-20-6-3 is available for immediate shipping. The NSN for part number is 5925011701532. This part is manufactured by Eaton Corp. It is described as Circuit Breaker. Would you like to request a quote for part number AM4-A3A3A3A2-30-30-20-6-3? Please fill out the form.
The form includes various important fields such as your contact details, Need Parts By, and Quantity. Please make sure to fill out all these fields accordingly before clicking to submit the form. Our experts will review your answers for Need Parts By and Quantity to calculate your quote.

Upload RFQ Sheet
If you have more than one item, upload your spreadsheet here
Characteristics Data of NSN 5925-01-170-1532, 5925011701532
MRC | Criteria | Characteristic |
---|---|---|
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, THREE, AND FOUR LINKED |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE FOUR |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.180 MINIMUM AT 200 PCT ALL LOCATIONS AND 1.800 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND HUMIDITY RESISTANT AND MOISTURE RESISTANT AND SHOCK RESISTANT AND VIBRATION RESISTANT |
CRTK | SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC AND 5.0 DC |
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND 30.0 DC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 8 THREADED STUD |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 2.468 INCHES MINIMUM AND 2.532 INCHES MAXIMUM |
ADAT | BODY WIDTH | 2.968 INCHES MINIMUM AND 3.032 INCHES MAXIMUM |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.906 INCHES MINIMUM AND 1.970 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.722 INCHES MINIMUM AND 0.782 INCHES MAXIMUM |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.030 INCHES MINIMUM AND 2.094 INCHES MAXIMUM |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.722 INCHES MINIMUM AND 0.782 INCHES MAXIMUM |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.108 INCHES MINIMUM AND 0.172 INCHES MAXIMUM |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.688 INCHES MINIMUM AND 2.752 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 4 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC THIRD LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC FIRST LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC SECOND LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 6.0 AMPERES AC FOURTH LOCATION |
Sought-After NSN Components List