Characteristics Data of NSN 5925-01-022-8122, 5925010228122
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 6.312 INCHES NOMINAL |
ADAT | BODY WIDTH | 2.750 INCHES NOMINAL |
ADAU | BODY HEIGHT | 3.140 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.620 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.380 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.620 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.375 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.710 INCHES NOMINAL |
AKPX | POLE QUANTITY | 2 |
APNQ | ARC QUENCHING METHOD | AIR |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CBME | III CUBIC MEASURE | 55.314 CUBIC INCHES |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 40.0 AMPERES AC ALL LOCATIONS AND 40.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 480.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 18000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 725.000 MINIMUM AT 100 PCT ALL LOCATIONS AND 1000.000 MAXIMUM AT 100 PCT ALL LOCATIONS AND 30.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 125.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 15.000 MINIMUM AT 250 PCT ALL LOCATIONS AND 60.000 MAXIMUM A |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 10.0 DEG CELSIUS MINIMUM ALL LOCATIONS AND 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 4 SCREW |