Buy D6761-1-20 Part of Saga Engineering Corp with NSN 5925-00-839-4689
MPN: D6761-1-20
Alternate P/N: D6761120
Manufacturer: Saga Engineering Corp
NSN: 5925-00-839-4689
Item Name: Circuit Breaker
CAGE Code: 58634
Part number D6761-1-20 is available for immediate shipping. The NSN for part number is 5925008394689. This part is manufactured by Saga Engineering Corp. It is described as Circuit Breaker. Would you like to request a quote for part number D6761-1-20? Please fill out the form.
The form includes various important fields such as your contact details, Need Parts By, and Quantity. Please make sure to fill out all these fields accordingly before clicking to submit the form. Our experts will review your answers for Need Parts By and Quantity to calculate your quote.

Upload RFQ Sheet
If you have more than one item, upload your spreadsheet here
Characteristics Data of NSN 5925-00-839-4689, 5925008394689
MRC | Criteria | Characteristic |
---|---|---|
ABHP | OVERALL LENGTH | 1.813 INCHES NOMINAL |
ABKW | OVERALL HEIGHT | 1.093 INCHES NOMINAL |
ABMK | OVERALL WIDTH | 0.750 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
APNQ | ARC QUENCHING METHOD | AIR |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC SINGLE LOCATION AND 20.0 AMPERES DC SINGLE LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC SINGLE LOCATION AND 30.0 DC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 AC SINGLE LOCATION AND 2000.0 DC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH-PULL |
CPRW | ACTUATOR FUNCTION | RESET |
CQJX | NOMINAL THREAD SIZE | 0.469 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 60.000 MAXIMUM AT 200 PCT SINGLE LOCATION AND 3.000 MINIMUM AT 300 PCT SINGLE LOCATION AND 15.000 MAXIMUM AT 300 PCT SINGLE LOCATION AND 1.500 MINIMUM AT 400 PCT SINGLE LOCATION AND 6.000 MAXIMU |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION PROOF |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
TTQY | TERMINAL TYPE AND QUANTITY | 2 SCREW |
AKPX | POLE QUANTITY | 1 |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 SINGLE LOCATION |
CPRQ | RESET METHOD | MANUAL |
THSD | THREAD SERIES DESIGNATOR | UNS |
Part D6761-1-20 With Different Manufacturers
Sought-After NSN Components List
Leading NSN Part Manufacturers